TM 10-4610-232-12
NOTE
Wait until filter has fully drained before removing nut (7).
(f) Loosen clamp (8) using ratchet wrench. With crescent wrench remove clamp (8), cover (9), gasket (10), nut
and washer (7), plate (11), retainer (12), 10 spring and seal assemblies (13), and 10 filter elements (14) from filter housing
(15). Discard filter elements. Replace gasket (10) if cut or damaged.
(g) Install 10 new elements (14). Then install 10 spring and seal assemblies (13), retainer (12) and plate (11).
(h) Install nut and washer (7) and tighten leaving approximately 1 inch between plate (11) and retainer (12).
(i) Check and clean out gasket sealing area. Install gasket (10), cover (9), and clamp (8). Tighten clamp with
ratchet wrench.
(j) Close drain (5) and vent (6).
(k) Start-up as described in para. 2-19 and resume operation.
Figure 2-56.1. Replace Outer Basket Strainer Screen
(MODEL ROWPU-1 ONLY)
Change 7 2-108.1 / (2-108.2 Blank)