Table 3-1. Direct Support Troubleshooting - continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
RAW WATER PUMP ASSEMBLY NO. 1
d.
If continuity is not measured through heater assembly, replace defective heaters (Paragraph 3-53)
and reset heater assembly.
e.
If continuity does not exist through K3 contacts (2-3) and/or 90-120 Ohms is not measured from A2
to Al, replace motor starter. Refer to Paragraph 3-61.
f.
If continuity is absent through wiring, tighten loose connections and/or replace defective wires.
3-69