TM 55-2090-201-14&P
4-37.
MOUNTING FRAME - TYPE C AND D SEPARATORS.
L O C A T I O N
I T E M
A C T I O N
R E M A R K S
NOTE
Allow the oil to discharge for approximately one to
two seconds after the oil disappears from the sight-
glass before closing the oil discharge valve.
(3) Open the water dis-
charge valve (6) and
close the oil dis-
charge valve (2 or
3) after the oil has
drained from the stage.
b. Stop the supply pump (1)
by turning the supply pump
selector switch (7) OFF.
C. Close the water discharge
valve (6).
d. To drain water from the
first (prefilter) stage
(4):
(1) Close the inlet valve
(8) located at the
inlet to the first
(prefilter stage (4)
and the intervessel
shutoff (9) valve
between the first
(prefilter) and
second stages.
(2) Open the drain valve
(10) at the base of
the vessel.