TM 10-461021510
TM 08580A10/1
Chemical Feed Pump Motor
Voltage
.
.
.
.
.
.
.
.
.
.
.
.
Current . . . . . . . . . . . . . . . . . . . . . . . .
Horsepower . . . . . . . . . . . . . . . . . . . . . .
Frequency
.
.
.
.
.
.
.
.
.
.
.
Revolutions Per Minute. . . . . . . . . . .
Duty
Cycle.
.
.
.
.
.
.
.
.
.
.
Chemical Feed Pump
Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drive . . . . . . . . . . . . . . . . . . . . . . . .
Multimedia Filter
Flow Rate. . . . . . . . . . . . . . . . . . . .
Backwash Flow Rate . . . . . . . . . .
Pressure Drop . . . . . . . . . . . . .
Cartridge Filter
Cartridge (8 cartridge tubes)
Length
.
.
.
.
.
.
.
.
Flow
Rate
.
.
.
.
.
Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . .
115/230 V ac, 1phase
6.2/3.1 amp (Army)
4.8/2.4 amp (MC)
1/3
60 Hertz
1725
Continuous
3.17 gallons/hr (12 liters/hr)
Electric motor
6.5 gpm/sqft
70 t0 120gpm (265 to 454 lpm)
5 psid (nominal) (3516 kg/sqm)
40 in (101.6 cm)
35 gpm (132.5 lpm)
2 t0 35 psid (1406 to 24,609
k g / s q m )
1-8.
PIPING IDENTIFICATION. The ROWPU piping is identified according to function by the following
colors:
Function:
Color:
Raw water
Black band
Backwash waste
Red band
Filtered water
Yellow band
Product water
Blue band
Brine discharge
Purple band
Brine Piping on R.O. pressure vessels
Purple band
Section III. TECHNICAL PRINCIPLES OF OPERATION
19.
WATER PROCESSING AND CHEMICALS. The ROWPU removes suspended solids (called
turbidity), chemicals, and solids held in solution (called dissolved solids), found in most fresh water and seawater
sources, to a level fit for human consumption, This is done by filtering with the aid of the reverse osmosis process,
and then additional purification using selected chemicals, Refer to figure 115 to follow the process described
below.
1-16