e. Repair or Redate.
(1) Replace damaged or unserviceable pump motor.
(2) Send damaged or unserviceable pump motor to Direct Support Maintenance for repair.
(3) Replace damaged or worn cables and cable hardware.
WARNING
Weight of R.O. pump is 251 pounds (1 12.95 kilograms).
Attempting to move it without proper equipment could cause
serious injury. Lift motor with equipment rated at one ton (0.91
tonne) or greater.
f. Installation. (Figure 2-49).
(1)
(2)
stand.
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
motor (20).
(16)
(17)
(18)
With proper equipment, place R.O. pump motor (20) onto R.0, pump assembly stand.
Install four lockwashers (19) and four bolts (18) into R.O. pump motor (20) and R.O. pump assembly
NOTE
If conduit box cover is in place, remove four screws (1), four
lockwashers (2), conduit box cover (3), and gasket (4) from
conduit box (22).
If previously removed, slip cable grip (17) over cable.
Insert motor leads through hole in conduit box (22).
Install conduit box (22) with bolts (15) and lockwashers (16).
Install ground wire lug (13) on grounding stud (21) in conduit box (22).
Install nut (12) on grounding stud (21).
Slip tagged wire lugs (10) over screws (11) on each set of wires.
Install flat washer (9), lockwasher (8), and nut (7) on screw (11) for each set of wires.
Remove tags from wires.
Wrap each screw and lug assembly with tape (6).
Using lacing cord, tie taped wires into bundle.
Carefully install wire bundle into the conduit box (22).
Hold conduit box cover (3) and new gasket (4) in place.
Install four lockwashers (2) and four screws (1) through conduit box cover (3) and gasket (4) into
Install R.O. pump motor sheave assembly in accordance with paragraph 277.
Install R.O. pump belts in accordance with paragraph 276.
Install R.O. pump belt shroud in accordance with paragraph 275.
2-92