TM 10-4610-239-10
TM 08580B-10/1
Table 2-5. Shutdown Position of Valve or Switch
Order
Valve or Switch
Position
1
CHEMICAL FEED PUMP (valves (fig. 2-68)
PRIME
2
CHEMICAL FEED CONTROL knobs (fig. 2-7)
8.5
3
REGULATE PRODUCT FLOW valve
OPEN
4
VENT PRODUCT WATER valve
OPEN
CAUTION
After opening the regulate product flow valve
fully, wait 5 minutes before opening vent
vessels valve.
5
VENT VESSELS valve
OPEN
6
VENT CARTRIDGE FILTER valve
OPEN
7
VENT PULSE DAMPENER valve
OPEN
8
VENT MULTIMEDIA FILTER valve
OPEN
9
R.O. PUMP switch
STOP
10
BOOSTER PUMP switch
STOP
11
CHEMICAL FEED PUMP switch
STOP
12
RAW WATER PUMPS NO. 2 switch
STOP
13
RAW WATER PUMPS NO. 1 switch
STOP
2-32.
OPERATION OF AUXILIARY EQUIPMENT.
WARNING
Operating noise level of the generator set can cause hearing damage.
Ear protectors, as recommended by the medical or safety officer, must
be worn when working near set.
Generator sets must not be operated in enclosed areas unless exhaust
discharge is properly vented to the outside. Be alert at all times during
operation for odors and exposure symptoms.
2-85