TM 10-4610-240-24
TM 08580C-24/2
TO 40W4-13-22
2-47.
FLOW METER (BRINE WATER) MAINTENANCE.
This task consists of:
a. Removal
b. Installation
INITIAL SET-UP:
Tools Required
General Mechanics Tool Kit (Appendix B, Section III, Item 4)
Material/Parts Required
Tape, Anti-seize (Appendix C, Section II, Item 30)
Tape, insulating (Appendix C, Section II, Item 32)
Gasket - M103873DO2
Lockwasher (2) - MS35338-139
Lockwasher (2) - MS35338-140
Equipment Condition
Reference
ROWPU shutdown (TM 10-4610-240-10).
Power shutdown (power source manual)
ROWPU piping drained (TM 10-4610-240-10).
REMOVAL
a.
Remove cap (1) from pipe section (3).
b.
Remove two nuts (10), lockwashers (9), flat washers (8), and screw (5).
c.
Loosen two nuts (6) and remove clamp halves (4).
d.
Remove two nuts (17) lockwashers (16), and bracket (15) from studs (20).
e.
Remove two nuts (11), screws (13), clamp halves (12), and gasket (14).
f.
Tilt pipe sections (3 and 18) and remove from control panel (21) with flowmeter (19) attached.
NOTE
Tag ends of pipe sections before removal.
g.
Place flowmeter (19) in vice and remove pipe sections (18) and (3) from flowmeter.
h.
Remove ring filler (2) and insulating tape (7) from pipe section (3).
2-182