TM 10-4610-241-10
TO 40W4-13-41
2-2. ROWPU CONTROLS AND INDICATORS- cont.
Table 2-1. ROWPU Controls and Indicators
Key
Control or Indicator
Function
1
Control Box Assembly
Indicator lamps; switches to start, operate and stop (including
EMERGENCY STOP) all pumps. (See figure 2-5 sheet 2, keys 25
through 44).
2
Panel Light
Provides light for inside of the ROWPU and for the control panel. It is
mounted on a movable bracket that can be pulled forward to provide
more light on the control panel.
3
In-Line TDS Monitor
Used to continually monitor quality of product water (see figure 2-5,
sheet 1).
4
Vent Cartridge Filter Valve
Vents air during filling and draining cartridge filter.
5
Vent Pulse Dampener Valve (Models
Vents air during filling and draining pulse dampener.
WPES-10, WPES-20 and WPES-30
only)
6
Vent Multimedia Filter Valve
Vents air during filling and draining multimedia filter.
7
Backwash Valve
Backwash valve has two positions: NORMAL and BACKWASH. In
NORMAL, the valve closes the backwash inlet and allows raw water to
flow through the ROWPU. In BACKWASH, the raw water inlet is
closed and water is allowed to flow through the backwash inlet. After
backwashing, the valve should be returned to the NORMAL position.
8
Multimedia Filter Gage
9
Waste Outlet
10
R.O. Vessels Gage
11
Raw Water Flow
12
Backwash Water Inlet
13
Raw Water Inlet
14
Ground Rod
15
Backwash Water Flow Gage
16
R.O. Pressure P.S.I. Gage
17
Brine Flow Meter
Indicates differential pressure across the multimedia filter.
Connection for waste water produced when backwashing.
Indicates differential pressure across the R.O. vessels.
Measures in gallons per minute the amount of water drawn in by raw
water pump(s) and fed into ROWPU.
Connection for backwash hose from backwash pump.
Connection for hose from raw water pumps.
Used to ground ROWPU. Protects personnel from electrical shock.
Measures amount of water flowing through multimedia filter during
backwash cycle.
Shows discharge pressure of the R.O. pump in pounds per square inch
(psi). Gauge reading depends on setting of REGULATE PRODUCT
FLOW valve.
Measures amount of brine flow from the ROWPU in gallons per minute
(gpm).
Change 2 2-9