TM 10-4610-241-24
TO 40W4-13-42
3-61. MOTOR STARTERS REPAIR - continued.
e.
Installation.
(1)
Motor starter K1
WARNING
High voltages in this equipment can cause serious injury or death. Be certain that
all power is removed before installing motor starter K1.
NOTE
Be sure to connect all wires as marked. White wires have markings (termination
points) stamped on wire by manufacturer. Red wires are not marked, and must be
installed as described.
(a)
Position motor starter injunction box and install with four screws (25), flatwashers (24), lockwashers (23) and
nuts (22).
(b)
Position wire (21), marked KI (N) on contact marked NC (bottom left) and install square washer (20) and
screw (19)
(c)
Position wire (18), marked K1, 2 on contact 2 of motor starter (top left set of contacts) and secure with square
washer (17) and screw (16).
(d)
Position wire (15), marked K1, 1 on contact 1 of motor starter (top left set of contacts) and secure with square
washer (14) and screw (13).
(e)
Position wires (11 and 12) marked K1, 1, COIL on coil contact of motor starter (center set of contacts, right
contact) and secure with square washer (10) and screw (9).
(f)
Position wire (8) marked AUX 1 on unmarked auxiliary contact 1 (bottom contact of auxiliary contacts to the
right of motor starter) and secure with square washer (7) and screw (6)
(g)
Position wire (5) marked AUX 2 on unmarked auxiliary contact 2 (top contact of auxiliary contact to the right of
motor starter) and secure with square washer (4) and screw (3).
(h)
Position large diameter wires (2) marked L1 thru L3 and T1 thru T3 on contacts marked L1 thru L3 and T1 thru
T3 on motor starter and secure with one screw (1) each.
3-344