TM 55-1930-209-14&P-19
Table 7-2. Preventive Maintenance Checks and Services for Compressed Air System (Continued)
B -
Before
D -
Daily
Q - Quarterly
D -
During
W -
Weekly
S - Semiannually
A -
After
M -
Monthly
A - Annually
INTERVAL
ITEM
PROCEDURES
EQUIPMENT
ITEM
TO BE
CHECK FOR AND HAVE
IS NOT READY/
NO.
INSPECTED
REPAIRED OR ADJUSTED
AVAILABLE IF
B D A D W M Q S A
AS NECESSARY
e.
Check receiver safety
valve on all com-
pressors (Barges 1, 2, and 3).
1) Pull up on safety link
on safety valveAir does not
in top of receiver. Air should escape
escape from
from valve.
valve.
WARNING
System MUST NOT be operated without
an operating receiver safety valve. In
the
event
that
the
compressor
continues to run beyond factory set
pressure, this valve reduces receiver
pressure to a sale level.
2)
If
air
does
not
escape, replace
receiver safety valve. This valve can
not be adjusted or repaired. Replace
as follows:
(a) Shut down air compressor sys-
tem.
(b) Redtag power panel 1 circuit
breaker 3P5 indicating,
"WARNING - DO NOT ACTIVATE.
REPAIRS BEING MADE."
(c) Unscrew safety valve.
(d) Screw in new safety valve (Barge
1 - P/N 9710-5332-00) (Barges 2
and 3 - P/N 91A033175-001)
wrench tight.
(e) Start air compressor system.
(f) When receiver pressure gauge
reads at least 100 psi, check
receiver safety valve by pulling
safety link. Air should escape from
receiver thru valve. If not, repeat
above procedures and install
another new safety valve. This
valve is NOT adjustable or
repairable.
(g) Remove red tag from power panel
1 circuit breaker 3P5.
7-19