TM 55-1930-209-14&P-3
a.
Always use new seals and gaskets before reassembling components disassembled for repair. Be sure to use
only the correct seals and gaskets and install them carefully to avoid damage.
b.
When replacing O-rings, make sure all surfaces are clean and free of dirt, grit, or foreign material. Prior to
installation, apply a thin coat of silicone grease to the O-ring. Protect O-rings by applying tape over threads,
sharp corners, and edges.
c.
To ensure a leak-proof joint when replacing gaskets, make sure mating surfaces are clean and free of old
gasket material, adhesive, oil, or grease.
d.
When replacing electrical components, follow proper procedures for soldering or crimping connections.
Check all grounding. Make sure current-carrying members are properly insulated to avoid short-circuiting.
Check for abrasions and chafing of insulation on wires and cables. Repair with tape or replace as necessary.
Table 4-1. ROWPU System Troubleshooting
Condition
Possible Cause
Suggested Action
1.
Low flow of seawater
a.
Valve RO18 not
a.
Open valve RO18
at flow rate indicator F1
fully open
b.
HP pump engine speed
b.
Adjust (paragraph 3-4
not adjusted correctly
steps q-s)
with throttle valve R07
c.
Seawater system not
c.
Troubleshoot sea-
providing proper flow
water system
of seawater
(TM 55-1930-209-14&P-2)
2.
Seawater appears
a.
Seawater filters
a.
Drain filters or
very cloudy in
clogged or seawater
clean seawater
seawater pump flow
strainers dirty
strainers
rate indicator Fl
(TM 55-1930-209-14&P-2)
3.
MEDIA FILTER OK light
a.
Bulb burned out
a.
Replace bulb (paragraph
on control station is out
4-8.1.7)
b.
Media filters clogged
b.
Backwash (paragraph 4-7.2)
4.
Pressure difference
a.
Media filters
a.
Backwash filters
between pressure
clogged
(paragraph 4-7.2)
gauges P1 and P2
exceeds 35 psi
b.
Valve RO4
b.
Open valve RO4
improperly positioned
5.
CARTRIDGE FILTER
a.
Bulb burned out
a.
Replace bulb (paragraph
OK light on ROWPU
4-8.1.7)
control station is
b.
Cartridge filter
b.
Replace cartridge
out
elements clogged
cage assembly (paragraph
4-7.1.1)
6.
Pressure difference
a.
Cartridge filter
a.
Replace cartridge
between pressure
elements clogged
cage assembly
gauges P2 and P3
(paragraph 4-7.1.1)
exceeds 12 psig
7.
Water sample
a.
Inadequate dose of
a.
Increase stroke
taken at valve RO8
coagulant
on coagulant pump
is cloudy
b.
Coagulant pump off
b.
Start pump at control
station by turning
coagulant pump ON/OFF
switch ON
c.
Coagulant drum empty
c.
Replace drum (paragraph
4-7.1.3) and prime pump
(paragraph 4-7.1.5)
4-2