TM 55-1930-209-14&P-5
Table 1-1. Major Components of Drinking Water System (continued)
Component
Function
Location
Motor controller
2 remote switches for discharge
pumps 1 and 2
Pump and storage tank selection
switch
Controls manual operation for
pressure set of pressure set
Control remote operation of discharge
pumps
Selects discharge pump and storage
tank whose liquid level switches
automatically start and stop discharge
pump
Void 3 port near filter water
ROWPU space on forward bulkhead
Void 3 port on aft bulk-head
1-8 Capabilities. The total onboard storage capacity Is 15,000 gallons plus 250 gallons reserve. The maximum
discharge pressure is 140 pounds per square inch (psi) and the maximum discharge rate with both ROWPU's operating
Is 300,000 gallons per day (gpd), 15,000 gallons per hour (gph), or 250 gallons per minute (gpm).
1-9 Limitations. The drinking water system shall not be operated in rough sea conditions exceeding Sea State 3. For
acceptable drinking water standards, the chlorine content must be from 5 to 7 parts per million (ppm) and the salinity
level must not be greater than 1500 ppm
1-10 Performance characteristics
a Drinking water discharge pump
Rating
260 gpm @250 ft
Revolutions
1,750 rpm
Rating
440 Vac, 3 ph, 60 Hz, 30 HP
Flow sensor capacity
600 gpm, 5 gpm
Pressure sensor rating
0-300 psi
1-8