TM 55-1930-209-14&P-9-1
2-1.2
Components of this system are listed in Table 2-1 and shown in engineering drawings listed in Appendix A.
2-2.
Capabilities. This system provides electrical power for operating barge equipment. Either of two 155 kW SSGs
provides sufficient electrical power to operate all systems onboard. The SAG provides sufficient power for barge occupancy
but not for major ROWPU systems operation. When onboard generator sets are not operating, power can be supplied
through the shore power receptacle from onshore or from another vessel. An emergency shutdown system is also provided
to stop individual systems or to stop all electrically powered equipment onboard. Paragraph 2-18 provides additional
information.
2-3.
Special limitations. This system must have sufficient fuel for diesel-powered generators and the generators must
be operational.
2-4.
Performance characteristics
a.
Shore power to switchboard 440 Vac, 60 Hz, 3 ph
b.
Generators to switchboard 440 Vac, 60 Hz, 3 ph
c.
Switchboard 440 Vac, 60 Hz, 3 ph
Table 2-1. Electrical Power System Major Components
Component
Quantity/Function
Location
Switchboard
1 - Controls and distributes
ROWPU space port bulkhead aft
electrical power
Shore power receptacle
1 - Receives power from outside
Stem weatherdeck portside
source
SSG
2 - Provides electrical power
Voids 4 port & starboard
SAG
1 - Provides electrical power
Void 4 starboard
Power panel 1
1 - Distributes 440 Vac power
ROWPU space port bulkhead forward
near door to weatherdeck
Power panel 2
1 - Distributes 440 Vac power
ROWPU space starboard bulkhead
forward of sliding door
Power panel 3
1 - Distributes 220 Vac power
ROWPU space forward bulkhead
Power panel 4 (Barge 1)
1 - Distributes 440 Vac power
ROWPU space starboard bulkhead
to heaters
Deck lighting panel
1 - Controls electrical power
ROWPU space starboard bulkhead
for deck lights
Void lighting panel
1 - Controls electrical power
ROWPU space starboard bulkhead
for void lights
near dayroom door
Receptacle panel
1 - Controls electrical power
Workshop aft bulkhead
to receptacle
Ground detector panel
1 - Indicates ground in 115 Vac
ROWPU space forward bulkhead
power system
Emergency shutdown
7 - Shut down electric-powered
See paragraph 2-18
equipment or total electric power
6- Shut down total electric
power
2-7