AUTOMATIC START/STOP SYSTEM
SYSTEMS OPERATION
AUTOMATIC START/STOP WIRING
COMPONENT ABBREVIATIONS
A
DC AMMETER
OPG
OIL PRESSURE GAUGE
ACS
ENGINE CONTROL SWITCH
OPR
LOW OIL PRESSURE RELAY
ALT
CHARGING ALTERNATOR
OPS
OIL PRESSURE SWITCH
AR
ARMING RELAY
OPT
OPTIONAL EQUIPMENT
ARX
AUXILIARY RELAY
OSR
OVERSPEED RELAY (IN DSS)
ASO
AIR SHUTOFF SOLENOID
OSS
OVERSPEED SWITCH (IN DSS)
OCT
OVERCRANK TIMER
PIL
PANEL ILLUMINATION LAMP
CB
CIRCUIT BREAKER
PLS
PANEL LAMP SWITCH
CCM
CYCLE CRANKING MODULE
PS
PINION SOLENOID
CCT
CYCLE CRANK RELAY
RR
RUN RELAY
CDT
COOL DOWN TIMER
SS
SHUTOFF SOLENOID
CDTR
COOL DOWN TIMER RELAY
SM
STARTER MOTOR
CRC
CYCLE CRANK LOGIC TIMER
TDR
TIME DELAY RELAY
CTS
CRANK TERMINATE SWITCH
TDX
TIME DELAY AUXILIARY RELAY
DSS
DUAL SPEED SWITCH (INCLUDES CTS AND OSS)
WT
WATER TEMPERATURE GAUGE SENDER
GS
GOVERNOR SWITCH
WTG
WATER TEMPERATURE GAUGE
GSM
GOVERNOR SYNCHRONIZING MOTOR
WTR
HIGH WATER TEMPERATURE RELAY
I
INITIATE CONTACT (REMOTE START)
WTS
WATER TEMPERATURE SWITCH
MS
MAGNETIC SWITCH (CRANK CIRCUIT)
*
INDICATES EQUIPMENT EXTERNAL TO CONTROL PANEL
OCR
OVERCRANK RELAY
O
TERMINAL STRIP POINT (CONTROL PANEL)
OP
OIL PRESSURE GAUGE SENDER
[ ]
TERMINAL STRIP POINT (GENERATOR TERMINAL BOX)
ê
RELAY CONTACT LINE NUMBER
NOTE A:
Terminals 13 and 14 of the generator box will be co-
nected to terminals 13 and 14 of the control panel when
the CDT is not supplied.
NOTE B:
Red jumper wire from terminal strip point number 4A to
4 in control pal must be removed when the cycle
cranking module (CCM) is used.
NOTE C:
Auxiliary relay (ARX) contacts are to be customer wired.
See Relay Contact Schematic.
NOTE D:
Dotted lines shown on Control Panel Wiring Schematic
show engine wiring.
NOTE E:
The overcrank timer (OCT) is to be adjusted to the 30
seconds setpoint (red dot). When cycle cranking (CCM)
is used the overcrank timer (OCT) is to be adjusted to
the 90 second setpoint (white dot).
NOTE F:
ACS switch contacts shown with switch in auto position.
NOTE G:
Jumper wire from terminal 72 to terminal 73 must be
removed when DC ammeter (A) is used.
NOTE H:
Jumper wire from terminal 13 to terminal 133 to be re-
moved if additional fault shutdown are added. Exam-
ples: reverse power relay or remote shutdown Insert a
normally closed switch between terminal 13 and termi-
nal 133.
16