TABLE NO. 2
The table below gives wire sizes based on an assumed wire distance of not over 25 feet from the invert-a-volt to the
batteries. At distances exceeding 25 feet, the DC wire size should be chosen to keep the voltage difference between the
inverter terminals and the battery at less than 1/2 volt when the inverter is fully loaded.
WIRE SIZE
DC INPUT
AC OUTPUT
A5l-l00-24
l4
l8
A5l -l00-48
l4
l8
A5l -l00-20
l8
l8
A5l - 250-24
l0
l8
A5l - 250-48
l4
l8
A5l - 250-l 20
l6
l8
A5l - 500-24
8
l6
A5l - 500-48
l0
l6
A5l - 500-l20
l4
l6
A5l - IK-24
6
l4
A5l - IK-48
8
l4
A5I - IK-l20V
l2
l4
A5I-I.5K-24V
(4)
(7)
A5I-I.5K-48V
8
l2
A5I- I.5K-20V
l0
l2
A5l - 2K-48
6
l0
A5l - 2K-l20
8
l0
A5l - 3K-48
4
8
A5l - 3K-l20
8
8
A5l - 4K-48
2
6
A5l - 4K-l20
6
6
A5l - 5K-48
2
6
A5I - 5K-l20
6
6
A5I-6K-48
l
6
A5l - 6K-l20
4
6
A5l - 8K-48
l/0
4
A5l - 8K-l20
4
4
A5I - I0K-48
2/0
4
A5I-I0K-l20
2
4
A5I - l2.5K-l20
I
2
A5I - I5K-I20
I
2
A51 - 20K-120
I/0
l