DATA SHEET 336
LA MARCHE
MODEL A33 CHARGER
SPECIFICATIONS
ELECTRICAL:
A.C. INPUT VOLTAGES:
120. 208. 240; 480 or 575 single phase, S0/60 cycles
208. 240. 480 or 575 three phase. 50/60 cycles Models
marked * are available in 3 phase only.
D.C. OUTPUT COMBINATIONS AVAILABLE:
D.C. amps. - 3 to 250
D.C. volts* - 6. 12. 24, 32, 36. 48, 130, or 260
*Nominal values. other D.C. voltages available.
MECHANICAL:
Overall dimensions and approximate shipping weights
are listed. Case specifications are subject to change and
where space requirements are critical it is best to check
the factory for latest dimensions.
FINISH: Base material pretreated with zinc phosphate.
Grey primer covering all base metal. Hammertone Grey
baked enamel finish coat.
STANDARD FEATURES SUPPLIED.
MOUNTING: Mounting flanges are supplied as part
of the cabinet back plate on wall mounted units.
I.Potentiometer for desired float and equalize charge
voltage adjustments.
2. Quality D.C. ammeter and voltmeter with 50
illivolt movement, 2% accuracy.
3. Power failure relay with terminals for connections
to a remote alarm system.
4. Fused A.C. input and D.C. output for complete
protection.
5. Convenient switch to transfer from float charge
to high rate equalize charge.
6. Internal terminal board for easy connection of
A.C. input, D.C. output and power failure
equipment.
7. One complete manual is supplied with each A33
charger. This manual includes and covers the
following
topics:
Technical
Operation,
Installation
and
Operating
Instructions,
schematic wiring
diagram.
parts
list,
case
drawing, trouble shooting and replacing silicon
diodes. The manual supplied is packed inside
the charger. Additional manuals are billed at the
rate in effect at time of purchase.
OPTIONAL ACCESSORIES:
See Accessory Price List
Ace.
Code .
040 0-24 hour equalizing timer.
041 0-72 hour equalizing timer.
030 Low D.C. voltage alarm relay.
032 High D.C. voltage alarm relay.
03H Low/High D.C. voltage alarm relay.
034 No current alarm relay.
Ground detection systems.
050 Voltmeter.
05 1 Relays.
052 Lights.
053 Switch & Lights.
IOA Individual float/equalize adjustments, specify
model A338.
060 A.C. pilot light.
091 Special paint.
094 Export packing. Ace
A.C. circuit breaker replacing fuse.
Remote meters and controls.
Special input voltages.
Manuals.
Dual voltage A.C. input.
104 Dual fusing for A.C. input and D.C. output re-
105 { placing single input and output fusing.
06E I1% meters replacing 2% meters.
Relay rack molting. (Consult factory for
applicable models.)
SAMPLE SPECIFICATIONS FOR MODEL A33
The charger to be furnished shall be the La Marche Mfg. Co. Model A33 or approved equal. The charger shall employ
transistor controlled magnetic amplifier circuits to provide continuous taper charging. This charger shall maintain rated
output voltage within I 1% from no load to full load with A.C. input variations of ::10%.
This charger shall have:
1.
2 ranges. Float at 2.17 V.P.C. and Equalize at 2.33
V.P.C. on lead-acid batteries. Both settings
adjustable from face of panel. (Nickel cadmium
1.4 V.P.C., float 1.55 V.P.C. equalize.)
2. Automatic A.C. line compensation.
3. Automatic overload protection (current limiting) 4.
Automatic D.C. voltage regulation.
5. Silicon diode full-wave rectifiers.
6.
Automatic surge suppressors.
7.
Power failure relay with remote indication connect
ing terminals. Single form "C".)
8.
D.C. ammeter and voltmeter with 50 millivolt
movement, 2%accuracy.
9.
Fused A.C. input and D.C. output. Separate, dual
fused output load terminals.