TM 55-2090-201-14&P
Table 4-3.
Organizational Maintenance Troubleshootng Chart,
Type C and D Separators (Sheet 2 of 3).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4.
Motor runs and kicks out.
Step 1.
Step 2.
Step 3.
Step 4.
5.
Pump fails to
Step 1.
Step 2.
Step 3.
Step 4.
Is system properly aligned?
Align system.
Check for excessive discharge pressure.
Is pre-
filter element clogged?
Is discharge line ob-
structed?
Replace element per paragraph 3-40.
Remove obstruction.
Inspect for loose connections.
Tighten.
Check for improper ventilation.
Increase ventilation.
pump or prime.
Check for closed valve in suction line.
Open closed valve.
Inspect for clogged strainer on inlet line.
Clean strainer per paragraph 3-29.
Inspect for broken flexible joint.
Report condition to General Support
Maintenance.
Pump still fails to operate.
Report condition to General Support
Maintenance.
4-6