• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
Direct Support Troubleshooting Guide (Continued) - TM-10-4610-232-34_40
Direct Support Troubleshooting Guide (Continued) - TM-10-4610-232-34_42

TM-10-4610-232-34 Water Purification Unit Reverse Osmosis 3 000 GPH Trailer Mounted Flatbed Cargo 22-1/2 Ton 8 Wheel Tandem Model No. WTA-060 Manual
Page Navigation
  19    20    21    22    23  24  25    26    27    28    29  
TM   10-4610-232-34 Table  2-1.  Direct  Support  Troubleshooting  Guide  (Continued) MALFUNCTION TEST  OR  INSPECTION CORRECTIVE   ACTION Step 1. Shut down ROWPU and generator. Refer to electrical drawings in Appendix D. Remove the wires from A3X/A3Y and A2X/A2Y on relay K21(REF: Interconnection diagram FO-2, Sheet 6). Check for continuity across each contact with the indicating plunger of K21 out. Push the indicating plunger in and check that there is no continuity across the contact. If the continuity checks are not as noted above, replace relay K21(para. 2-23). Step 2. Check the wires that were removed in step 1 for looseness or damage at their preceding connections. Repair any loose or damaged wires (para. 2-20). 3. Feed high pressure alarm is on at less than 900 psig, or, is not on and system pressure Is more than 960 psig. Test feed high pressure switch (PSH5) (REF: Interconnection diagram FO-2, Sheet 14) for accuracy. Disconnect P24 (REF: Interconnection diagram FO-2, Sheet 14) from the pressure switch panel. Disconnect the pressure sensing line from the switch. Remove the cover on the switch and tag/remove the wires from the pressure switch. Check for internal leakage, Set a multi meter to the Ohms x 1 scale and attach the leads to the switch terminals that the wires were on. Connect a dead-weight tester or another known calibrated pressure control device to the switch pressure (or inlet) port. The multi meter should read zero resistance with no pressure on the inlet pressure port. Slowly apply pressure to the switch. The switch should open on an increasing pressure of 940 to 960 psig. (a) Replace the switch if there is internal leakage (para. 2-27). (b) Replace the switch if testing indicates it is actuating outside of the listed limits above (para. 2-27). (c) Refer to pressure gauge troubleshooting if the switch is actuating within the listed limits above. 4. Product high pressure switch does not work. (Ref. Schematic diagram FO-1, sheet 9, schematic lines 905-906). NOTE This switch is factory set to open at 40 psig. NOTE Refer to malfunctions 5 and 6 for further troubleshooting procedures. Step  1.  Shutdown  ROWPU  and  generator.  Refer  to  the  electrical  schematic  Appendix  D.  Check  continuity,  point-to- point,  from  J24A  to  J24E  (REF:  Interconnection  diagram  FO-2,  Sheet  14). (a)  Repair  any  damaged  or  loose  wires  (para.  2-28). (b) Replace/repair connector J24 if faulty (para. 2-28). (c) Replace PSH6 (REF: Interconnection diagram FO-2, Sheet 14), if it shows an open circuit (para, 2-27). Step 2. Shut down ROWPU and generator. Refer to electrical drawings in Appendix D. Check continuity, point-to- point, from transformer T1(X1) (REF: Interconnection diagram FO-2, Sheet 10) to J11A (REF: Interconnection diagram FO-2, Sheet 9). Repeat the procedure from T1(X2) to relay K22(K2) (REF: Interconnection diagram FO-2, Sheet 6). Remove the K1/K2 wires on K22 before testing. (a) Repair any loose or damaged wire (para. 2-20). (b)  Replace  circuit  breaker  CB7  or  CB10  (REF:  Interconnection  diagram  FO-2,  Sheet  8)  if  either  is  open (para.  2-23).  Normally  closed. (c)  Replace  emergency  stop  PB3  (REF:  Interconnection  diagram  FO-2,  Sheet  11)  if  open  (para.  2-22). (d) Replace/repair connector J11 if faulty (para. 2-21). Step 3. Check continuity, point-to-point, from J11E to K22(K1). Depress the indicating plungers on K6 (REF: Interconnection diagram FO-2, Sheet 7) and K22 when testing continuity across their contacts. (a) Repair any loose or damaged wire (para. 2-20). (b) Replace/repair connector J11 if faulty (para. 2-21). (c) Replace relay K6 or K22 if their set of contacts does not show continuity when the indicating plunger is depressed (para. 2-23). (d) Replace relay K22 if all the continuity checks are good (para. 2-23). 2-22 Change 1







Western Governors University

Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved. Design by Strategico.