TM 10-4610-239-10
TM 08580B-10/1
CAUTION
If raw water hoses freeze, poor water flow will reduce pressure in R.O.
pump. The R.O. PUMP LOW PRESSURE lamp will come on and R.O.
pump will shut itself off. Bring hoses under cover until ice melts.
NOTE
The ROWPU produces less product water when the temperature of raw
water drops.
b.
When the ROWPU is shut down during cold weather (temperature falls below 32 °F (0 °C), remove the R.O.
elements (para. 3-4) . Store the elements indoors or in a tent where the temperature is above freezing and allow them to
dry. Drain all water from ROWPU as follows:
WARNING
Make sure drained water runs toward lower ground (downstream) as far
from the raw water source as possible.
(1)
Drain ROWPU pipe, filters, and connections:
(a)
Open seven drain valves (para. 2-23a).
(b)
Open five vent valves (para. 2-23b).
(c)
Facing trailer from towing end, jack-up left side to permit maximum water drainage through drain
valves.
(2)
Drain R.O. pump as described below:
CAUTION
Do not operate R.O. PUMP JOG switch (42, fig. 2-4) for more than 5
seconds at a time. You will damage pump if you do.
NOTE
The JOG switch can be used when the R.O. pump LOW PRESSURE
lamp is on.
(a)
After water stops flowing out of drains, set R.O. PUMP JOG switch to JOG. Hold it there for 3 to 5
seconds to force water from pump.
(b)
Repeat operation of R.O. PUMP with JOG switch until no more water comes from the DRAIN
PULSE DAMPENER drain (fig. 2-41).
(c)
Disconnect plastic tubing from bottom of R.O. vessels so they can drain. Reconnect tubing when
vessels are fully drained.
2-101