TM 10-4610-239-10
TM 08580B-10/1
(1)
Slide clamp over end of one section of 3/4 in. x 80 in. flexible tubing. Attach tubing to adapter on gate
valve and close clamp.
(2)
Slide clamp over other end of tubing.
(3)
Remove plug from INLET port on FOR USE WITH CHEMICALLY CONTAMINATED WATER cartridge
and insert adapter.
(4)
Attach tubing to adapter on INLET port and close clamp.
(5)
Cut one section of 3/4 in. x 80 in. flexible tubing to a maximum length of 24 in.
(6)
Slide clamp over end of tubing.
(7)
Remove plug from OUTLET port on FOR USE WITH CHEMICALLY CONTAMINATED WATER
cartridge and insert adapter into cartridge.
(8)
Attach tubing to adapter on OUTLET port and close clamp.
(9)
Remove plug from INLET port on FOR USE WITH RADIOACTIVE CONTAMINATED WATER cartridge
and insert adapter into cartridge.
(10) Slide clamp over end of tubing.
(11) Attach tubing to adapter on INLET port and close clamp.
(12) Slide clamp over end of second section of 3/4 in. x 80 in. flexible tubing.
(13) Remove plug from OUTLET port on FOR USE WITH RADIOACTIVE CONTAMINATED WATER
cartridge and insert adapter.
(14) Attach tubing to adapter on OUTLET port and close clamp.
f.
Complete connection of NBC cartridge to second raw water tank (fig. 2-83).
(1)
Slide clamp over remaining end of 3/4 in. x 80 in. flexible tubing.
(2)
Insert adapter into tubing and close clamp.
(3)
Attach shoulder bushing, pipe coupling, and straight adapter to 1 1/2 in. discharge hose and connect to
second raw water tank (fig. 2-83).
NOTE
Do not operate chlorination feed pump during NBC operation.
g.
During NBC operation, it is necessary to chlorinate the second tank by hand.
h.
With the exception of the chlorination feed pump, operate the ROWPU using normal operating procedures.
i.
Change the cartridges after every 100 hours of operating time.
2-106