TM 10-4610-240-24
TM 08580C-24/2
TO 40W4-13-22
2-62. CABLE ASSEMBLY (R.O. PUMP) MAINTENANCE.
This task consists of:
a. Removal
b. Test
c. Installation
INITIAL SET-UP:
Tools Required
General Mechanics Tool Kit (Appendix B, Section III, Item 4)
Material/Parts Required
Tape, Anti-seize (Appendix C, Section II, Item 30)
Tape, Electrical (Appendix C, Section II, Item 31)
Equipment Condition
Reference
ROWPU shutdown (TM 1-4610-240-10).
Power shutdown (TM 10-4610-240-10).
REMOVAL
a.
Disconnect cable connector (12) from unit.
b.
Remove four screws (23), star washers (22), cover (21), and gasket (20) from conduit box (19).
c.
Pull slack in three wire bundles (6) from conduit box (19). Remove twine (5) and electrical tape (4) from
each bundle.
NOTE
There are three wire bundles in conduit box. All are disassembled the same
One is shown, the others are similar.
Tag wires by set before removal.
d.
Remove nut (7), lockwasher (8), flat washer (10), and two wire lugs (9) from screw (11).
e.
Remove screw (3) and ground wire (1) at wire lug (2) from conduit box (19).
f.
Unscrew cable connector (14) from elbow (15).
g.
Carefully pull wires (16) from conduit box (19) and elbow (15), and remove cable (13) from unit.
h.
If required, remove four screws (24), starwashers (25), conduit box (19) and gasket (18) from motor (17).
i.
If required, remove elbow (15) from conduit box (19)
2-220