TM 10-4610-240-24
TM 08580C-24/2
TO 40W4-13-22
2-68. CHEMICAL FEED PUMP MAINTENANCE - continued.
INSTALLATION
a. Position chemical feed pump (21) on stand (23).
b. Install four screws (22), flat washers (24), lockwashers (25) and nuts (26).
NOTE
One suction and discharge flexible hose is shown. Other suction and discharge flexible hoses are
similar.
c. Place clamp (33) on flexible hose (32).
d. Connect flexible hose (32) to adapter (34). Position and tighten clamp (33) onto hose.
e. Place clamp (37) on flexible hose (36).
f. Connect flexible hose (36) to adapter (35). Position and tighten clamp (37) onto hose
g. Feed wiring (5) into conduit box (19)
h. Position seal (6) in sealing grip (4) and screw sealing grip into conduit box (19).
i. Position ground lug (17) on conduit box (19) and install screw (16).
j. Install screw (7), flat washer (8), lockwasher (14), and nut (13) on lugs (9) of each wire set (18). Be sure wiring in
each wire set (18) is connected as tagged during removal.
k. Wrap wire sets (18) with tape (20) Secure ends of tape with twine (15).
l. Install gasket (12), cover plate (11) and four screws (10) on conduit box (19).
m. Position two brackets (31) (upper and lower) on upright frame (29) and install four screws (30), lockwashers (28)
and four nuts (27).
n. Operate ROWPU. Check for leaks and proper operation (TM 10-4610-240-10).
2-244