TM 10-4610-241-24
TO 40W4-13-42
2-54.
CABLE ASSEMBLY (R.O. PUMP) REPLACE.
This task consists of:
a.
Removal
b.
Test
c.
Installation
INlTlAL SET-UP:
Tools Required
General Mechanics Tool Kit (Appendix 13, Section III, Item 4)
Multimeter (Appendix B, Section III, Item 3)
Material/Parts Required
Tape, Anti-seize (Appendix C, Section II, Item 19)
Tape, Electrical (Appendix C, Section II, Item 20)
Twine (Appendix C, Section II, Item 27)
Lockwashers, Seals and Gaskets (TM 10-4610-241-24P)
Equipment Condition
Reference
Power shut down (Power Source Manual).
a.
Removal.
(1)
Disconnect cable assembly (21) from ROWPU.
(2)
Remove screw (1), lockwasher (2) and clamp (3) from motor mounting plate (29).
(3)
Remove four screws (4), lockwashers (5), cover (6) and gasket (7) from conduit box (24).
(4)
Pull three wire sets (8) from conduit box (24). Remove twine (9) and electrical tape (10) from each set.
NOTE
There are three wire sets in conduit box. All are disassembled the same.
One is shown, the others are similar.
Tag wires by set before removal. If tagged parts are to be replaced, be sure
to transfer tags to replacement parts before discarding defective parts or
turning them in to Supply.
(5)
Remove nut (11), lockwasher (12), flat washer (13), and two wire lugs (14) from screw (15).
(6)
Remove screw (16) and ground wire (17) from conduit box (24).
(7)
Unscrew nut (20) from elbow (26).
(8)
Carefully pull wires from conduit box (24).
(9)
Remove seal (18), seal ring (19) and nut (20) from cable assembly (21).
2-208