TM 10-4610-241-24
TO 40W4-13-42
2-56.
CABLE ASSEMBLY, W40 (GENERATOR) REPLACE (MODEL WPES-10)
This task consists of:
a.
Removal
b.
Test
c.
Installation
INITIAL SET-UP:
Tools Required
General Mechanics Tool Kit (Appendix B, Section II, Item 4)
Multimeter (Appendix B, Section III, Item 3)
Equipment Condition
Reference
Power shut down (Power Source Manual).
a.
Removal.
WARNING
Lethal voltages are present at output lugs of generator during operation. Do not
attempt to connect or disconnect load leads while either the generator or the
ROWPU are powered up or while the generator is paralleled to another generator
which is in operation.
(1)
Open access cover (1) to gain access to generator terminal lugs.
(2)
As necessary, remove six screws (2), lockwashers (3), plastic cover (4) and standoffs (5).
(3)
Loosen four terminal nuts (6), and disconnect three wires (7) and wire bundle (8) from terminal lugs.
(4)
Loosen draw string on dust boot (9) and pull power cable (10) through dust boot, away from
generator.
(5)
At ROWPU junction box (11), unscrew connector nut (12) and disconnect cable assembly (10) from
junction box.
(6)
Remove cable assembly (10) from ROWPU, pulling from plug (12) end.
2-216