TM 10-4610-241-24
TO 40W4-13-42
Table 3-1. Direct Support Troubleshooting- continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
CHEMICAL FEED PUMP - continued
b.
If continuity is absent through K7, replace motor starter. Refer to Paragraph 3-61.
c.
If continuity is absent through circuit breaker, CB7 (CB7 ON), replace CB7. Refer to Paragraph 3-
53.
d.
If continuity is absent in wiring, tighten loose connections and/or replace defective wire.
3-39