TM 10-4610-241-24
TO 40W4-13-42
3-33. CABLE ASSEMBLY, W49 (FILTER CONTROL) REPAIR - continued.
c.
Inspection.
For inspection procedures, refer to TM 43-0158/TO 1-1A-15 (Air Force).
d. Test.
Check cable assembly for continuity and shorts, using cable wiring schematic (opposite page) as a guide.
e. Repair.
(1)
Replace lockwashers and other parts if unserviceable.
(2)
For repair procedures, refer to TM 43-0158/TO 1-lA-15 (Air Force).
f. Installation.
(1)
Install nut (20), seal ring (19), seal (18), adapter (17) and gasket (16) on cable assembly (21).
(2)
Feed cable assembly (21) into control box thru cutout in top of box and pull wires thru to reach terminal
board TB5 (7) and hole for screw (13).
(3)
Install nut (15) to secure adapter (17) to control box (28)
(4)
Using screws (5), install four lugs (6) of cable assembly (21) to terminal board TB5 (7) as follows:
White wire
-
TB5-2
Red wire
-
TB5-4
Blue wire
-
TB5-5
Green wire
-
TB5-6
(5)
Install screw (13), lockwasher (14), ground lugs (11 and 12), flatwasher (10), lockwasher (9) and nut (8) to top
of control box (28).
(6)
Position seal (18) inside of adapter (17) and seal ring (19) inside of nut (20) and connect nut to adapter.
(7)
Secure cable assembly (21) to back side of control panel with clamp (25), screw (24), lockwasher (23) and
nut (22).
(8)
Position control box cover (4) on control box (28) and install 14 screws (1), lockwashers (2) and flat washers
(3).
(9)
Route connector (26) to cable assembly (27) and connect to cable assembly (27).
(10)
Secure loose hanging cable to frame with cable ties as required.
3-194