TMI 10-4610-244-13
TM 09476B-13/1
Table 2-1.
Operation Preventive Maintenance Checks
and Service for Hypochlorination Unit
LOCATION
NOT FULLY
ITEM
ITEM TO BE
MISSION CAPABLE
NO
INTERVAL
CHECK/SERVICE
PROCEDURES
IF:
1
Before
Cover
Inspect for tears, holes
2
Before
Camlocks:
Inspect gaskets for nicks or deterioration
Gaskets are brittle or cracked
gaskets
3
Before
Ball valves
Inspect for free movement of valve lever
Valve lever does not move
4
Before
Sight assembly
Inspect casing for cracks and screws.
Cracks
5
Before
Lines and fittings`
Inspect lines for evidence of deterioration
Leaks
Inspect fittings for cracks or looseness
WARNING
Death or severe injury can occur from
explosion, fire, or chlorine gas caused
by contamination of hypochlorite
solution with organic matter, or other
chemicals. Use only clean, dry
utensils when handling solution. Do
not add solution to any dispensing
device containing residue or another
substance.
6
Before
Reservoir
a. Inspect reservoir and ensure it is com-
Contaminants are present
pletely clean, dry, and has no foreign
matter.
b. Inspect reservoir for dents, cracks, holes
Unable to hold 5 gallons of
or other damage.
Solution without leaking.
7
Before
Foot valve
Inspect strainer for clogging or damage
Strainer cracked, clogged
and not cleanable
8
Before
Accessory box
Inspect for dents, broken latch, broken lid
Hinges, or large holes
9
Before
Chlorine analysis kit
Inspect for cracks or breaks to comparator,
Comparator damaged, test
broken or missing test vials: ensure kit
vials broken or missing, less
contains several reagent tablets (mimimum
than 10 reagent tablets
10)
2-6