ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
0003 00
DESCRIPTION AND THEORY OF OPERATION
THEORY OF OPERATION
Product Flow Element FE-501 (mounted in the piping) and Product Flow Transmitter FT-501 (mounted in
the instrument/solenoid panel; see Figure 5) measure product flow. This flow is displayed at the OCP.
Product Utility Valve V-511 is used for filling chemical buckets and general use.
Hypochlorite Injection Check Valve V-633 injects a measured amount of calcium hypochlorite into the
product water flowing to the product water distribution system. This chemical chlorinates the product
water to kill and prevent the growth of algae and bacteria in the product water. (See Chemical Injection
System for further explanation.)
Product Water Check Valve V-512 prevents the flow of chlorinated product water back into the RO when
not in operation.
Four 10-ft. sections of blue-banded suction hose are connected to the product water outlet to discharge
product water to a distribution tank.
HYPOCHLORITE
PRODUCT RELIEF VALVE RV-501
PRODUCT VACUUM BREAKER VB-501
INJECTION CHECK
VALVE V-633
3-WAY VALVE
LOW RANGE
PRODUCT FLOW ELEMENT FE-501
ELEMENT CE-501A
PRODUCT MANIFOLD
PRODUCT
OUT
PRODUCT WATER
CHECK VALVE V-512
PRODUCT UTILITY VALVE V-511
PRODUCT PRESSURE GAUGE PI-5O1
Figure 14. RO System: RO Vessels to Product Out.
0003 00-17