ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
0003 00
DESCRIPTION AND THEORY OF OPERATION
THEORY OF OPERATION
Air Manifold Assembly
The Air Manifold Assembly is located in the Instrument/Solenoid Panel Box. The manifold is comprised of
six solenoid valves that are activated by the PLC to operate automatic valves in the TWPS. The solenoid
valves and the automatic valves that they control are as follows (see Figure 22):
- Solenoid Valve XV-904 controls 100 psig air to MF Main Feed Valve V-111
- Solenoid Valve XV-905 controls 100 psig air to MF Upper Feed Inlet Valve V-112
- Solenoid Valve VX-906 controls 100 psig air to MF Lower Feed Inlet Valve V-113
- Solenoid Valve XV-907 controls 100 psig air to MF Upper Shell Outlet Valve V-401
- Solenoid Valve XV-908 controls 100 psig air to MF Lower Shell Outlet Valve V-402
- Solenoid Valve XV-909 controls 100 psig air to MF Upper Filtrate Outlet Valve V-201
MF UPPER FEED INLET
VALVE V-112
INSTRUMENT/SOLENOID
PANEL BOX
MF LOWER FEED INLET
VALVE V-113
AIR MANIFOLD
ASSEMBLY
MF LOWER SHELL
OUTLET VALVE V-402
MF UPPER SHELL OUTLET
VALVE V-401
MF UPPER FILTRATE
OUTLET VALVE V-201
FILTRATE FLOW
CONTROL VALVE V-202
MF MAIN FEED
VALVE V-111
100 PSIG AIR
FROM SECTION 6
FEED FLOW
CONTROL PANEL
Figure 22. Air Manifold Assembly.