ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
0014 00
OPERATOR INSTRUCTIONS
INITIAL START-UP OR START-UP WITH THE SYSTEM FULLY DRAINED
OPERATION UNDER USUAL CONDITIONS
13. Set the stroke dial to 60%.
14. Turn the Bisulfite Pump switch on the OCP to AUTO.
PRIMING VALVE
BLACK KNOB
SPEED DIAL
STROKE DIAL
Figure 3. Chemical Pump Controls.
ESTABLISHING RAW WATER FLOW WITH BOTH RAW WATER PUMPS
NOTE
If only the electric raw water pump is deployed, see the procedures for "Establishing Raw
Water Flow with Only the Motor-Driven Raw Water Pump" that immediately follow these
procedures for "Establishing Raw Water Flow with Both Raw Water Pumps".
1. Set valve positions as follows (see Figure 4 for valve location):
a. Partially OPEN Raw Water Flow Control Valve V-107 on Adaptor A-05.
b. Fully OPEN Vent Valve V-102 on Adaptor A-02.
c. Check that pump Drain Valve V-103 on the diesel-driven pump skid is closed.
2. Disconnect the pump vent hose from the top of Adaptor A-02.
3. Use the priming pitcher to pour water through Vent Valve V-102 until the pump case is full.
4. Reconnect the vent hose.
DRAIN VALVE V-103
RAW WATER FLOW CONTROL VALVE V-107
ADAPTOR A-01
CHECK VALVE
VENT VALVE V-102
ADAPTOR A-02
PUMP VENT
HOSE
ADAPTOR A-05
V-104
Figure 4. Raw Water System with Both Raw Water Pumps.
0014 00-6