ARMY TM 10-4610-309-14
MARINE CORPS TM10802A-14/1
0023 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
OPERATOR INSTRUCTIONS
REVERSE OSMOSIS SYSTEM DETERGENT CLEANING OPERATION
UNDER USUAL CONDITIONS
4) Connect Adaptor A-12 to the A-16 Adaptor on the waste tank with the female end
exposed and close the valves on these two adaptors.
5) Make sure Valve V-706 on the other Adaptor A-16 on the waste tank is closed.
CLEANING WASTE TANK
A-16
A-10
A-16
TOP
VALVE V-706
VALVE V-706
2 X 10 S-HOSES
VIEW OF
TWPS
4 X 5 S-HOSE
A-12
VALVE V-705
Figure 3. RO Detergent Cleaning Waste Hose Set-Up with the Cleaning Waste Tank.
e. If not using the cleaning waste tank, set up the cleaning waste hoses as follows (see
Figure 4):
1) Connect a 2 x 10, red-banded, cleaning waste suction hose to Adaptor A-10.
2) Connect one 50-foot, green banded, raw water discharge hose to the 2 x10, red-
banded cleaning waste hose.
3) Connect one 2x10, red-banded, cleaning waste suction hose to the other end of
the 50-foot hose.
4) Connect Adaptor A-12 to the end of the second cleaning waste hose.
5) Close Adaptor A-12 Valve V-705.
6) Direct A-12 discharge into a depression in the ground away from the TWPS.
A-10
TOP
VIEW OF
TWPS
2 X 10 S-HOSE
4 X 5 S-HOSE
2 X 50 D-HOSE
A-12 VALVE V-705
2 X 10 S-HOSE
Figure 4. RO Detergent Cleaning Waste Hose Set-Up Without the Cleaning Waste Tank.
4. Remove the 3-in.hose from the TWPS inlet and cap the inlet.
5. Prepare water for RO detergent cleaning as follows (see Figure 5 for valve location):
a. Be sure Main RO Feed Tank Drain Valve V-412 is closed.
b. Open Clean Mixing Valve V-703.
c. Close HP Pump Inlet Valve V-212.
0023 00-4