ARMY TM 10-4610-309-14
MARINE CORPS TM10802A-14/1
0026 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
OPERATOR INSTRUCTIONS
MICRO-FILTRATION SYSTEM PRESERVATION OPERATION UNDER
USUAL CONDITIONS
RO FEED PIPING
DRAIN VALVE V-304
HPP OUTLET
DRAIN VALVE V-302
RO FEED TANK MAIN DRAIN VALVE V-412
RO FEED TANK
AUXILIARY DRAIN VALVE
RO FEED PUMP DRAIN VALVE V-211
V-210
Figure 6. Valves to Flush RO Feed Tank After MF Preservation Flush.
12. End the MF Caustic Preservation Flush for Extended Shutdown as follows:
a. If using the cleaning waste storage tank, perform the following steps:
1) Close valves V-705 and V-706 on Adaptors A-12 and A-16 that are connected
together on the cleaning waste tank (see Figure 2 for valve location).
2) Make sure the A-16 adaptor valve V-706 on the other side of the waste tank is
closed.
3) Disconnect Adaptor A-12 from the Adaptor A-16.
4) Direct the cleaning waste hose into an empty bucket, open Adaptor A-12 Valve
V-705 and drain the contents of the hose into the bucket.
5) Open the top of the waste tank and empty the bucket into the waste tank. Then
close the tank.
0026 00-8