ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
0052 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
UNIT MAINTENANCE PROCEDURES
REVERSE OSMOSIS SYSTEM
NOTE
Make sure to thread the outlet pipe into the outlet port of the pressure control
valve. An arrow on the side of the Main Pressure Control Valve HCV-401 points to
the outlet port of the valve. With the valve open, the valve handle of Auxiliary
Pressure Control Valve HCV-401A points to the outlet port of the valve.
b. Wrap antiseizing tape on the outlet pipe threads and screw the outlet pipe into the outlet
port of the new pressure control valve.
c. Wrap antiseizing tape on the inlet pipe threads and thread the new pressure control valve
onto the inlet pipe.
d. Install the hose clamp and outlet hose over the end of the outlet pipe and tighten the
clamp.
OUTLET PIPE
OUTLET HOSE
HOSE CLAMP
MAIN PRESSURE
INLET PIPE
CONTROL VALVE HCV-401
OUTLET HOSE
HOSE CLAMP
INLET PIPE
OUTLET PIPE
AUXILIARY PRESSURE
CONTROL VALVE HCV-401A
Figure 12. Main Pressure Control Valve HCV-401 Replacement.
Pressure Recovery Turbocharger PRT-1 Replacement:
Parts (TM 10-4610-309-24P):
Pressure Recovery Turbocharger
1-in. grooved coupling gasket
Material:
Corrosion preventive compound (WP 0079, Table 1, item 17)
Equipment Condition:
TWPS in Standby Shutdown With Drain-Down
Army: TWPS main breaker off
Marine Corps: TWPS disconnected from power source
0052 00-17