TM 5-4610-233-13&P
1-7. QUALITY ASSURANCE/QUALITY CONTROL (QA/QC). Maintenance standards for the hypochlo-
rination unit are given in the preventive maintenance sections and the maintenance chapters of this manual.
By performing PMCS and the maintenance procedures, quality control of the equipment will be maintained.
1-8. SAFETY, CARE, AND HANDLING. Observe all WARNINGS, CAUTIONS, and NOTES in this
manual. This equipment can be dangerous if these instructions are not followed.
Section Il. EQUIPMENT DESCRIPTION AND DATA
1-9. EQUIPMENT CHARACTERISTICS, CAPABILITIES, AND FEATURES.
Characteristic
Placed in a water supply line, will chlorinate water flowing through the line unattended for a minimum
of 2 hours.
Capabilities and Features
Feed hypochlorite solution in direct proportion to waterflow rate.
Portable frame-mounted.
Chlorinates waterflow rate from 2 to 350 gallons per minute.
Uses water pressure as power source.
1-10. LOCATION AND DESCRIPTION OF MAJOR COMPONENTS. See figure 1-2.
a. Four-Inch Manifold (1). A 4-inch diameter pipe for connection to a water supply line. The manifold
provides lateral outlets to power the solution feed pump and permit hypochlorite solution injection to the water-
flow.
b. Range Adjusting Valve (2). Mounted in the manifold and used to bypass enough waterflow through
the water meter to operate the solution feed pump.
c. Flow Controller (3). A mechanical flowmeter modified with a gear box and a control pilot valve to
operate the solution feed pump.
d. Solution Feed Pump (4). A hydraulically operated positive displacement proportioning pump.
e. Reservoir Tank (5). A 6-gallon plastic tank holding the hypochlorite and water solution.
1-2
Change 1