WARNING
TM 5-6630-215-12
e.
A summary of the maximum allowable raw water constituents for
use when determining the preliminary type of process or processes in
the treatment of the raw water source is contained in table 2-8.
Table 2-8. Maximum Allowable Raw Water Constituents
Test
Paragraph
2-21a
2-21b
2-21h(4)
2-21c
2-21e
2-21e(1)
2-21g(6)
2-21d
2-21h
2-21f
2-21i
Constituent
Alkalinity
Chlorides
Chloride, Demand
Color
Hardness, Total
Calcium
Magnesium
pH
Sulfate
Total Dissolved Solids
Turbidity
Coagulation
No Limit
250 mg/l
No Limit
No Limit
250 mg/l
250 mg/l
125 mg/l
No Limit
250 mg/l
500 mg/l
No Limit
Ion
Exchange
No Limit
3000 mg/l
No Limit
No Limit
2000 mg/l
2000 mg/l
125 mg/l
No Limit
1500 mg/l
3000 mg/l
*5 Units
Distillation
No Limit
No Limit
No Limit
No Limit
No Limit
No Limit
No Limit
No Limit
No Limit
No Limit
No Limit
*If the turbidity exceeds 5 units, the raw water source must be pretreated using the coagulation process
2-21a(2).
Dangerous chemicals are provided in these kits.
Death, health hazards or injuries such as severe
burns,
impaired vision and internal tissue
destruction may be experienced if personnel fail
to observe precautions.
Do not allow reagents, buffer solutions or acids
to come in contact with skin or eyes.
Do not
ingest solutions, tablets, droplets or spillage
from lab-ware.
Do not inhale fumes from products or mixing
reactions.
Cyanide is extremely poisonous.
Potassium cyanide should be stored away from
water and acids.
Always add Cyanide AFTER ADDING
Potassium Hydroxide and NEVER BEFORE.
Many products furnished are highly inflammable,
some have explosive potential.
Most acids are
corrosive.
2-53