TM 55-1930-209-14&P-1
9-16 Shutdown procedure
NOTE
Shutdown procedure is for normal operation and short downtime. For extended
shutdown times, see TM 55-1930-209-14&P-4.
a.
Turn metering pump control MANUAL/OFF/AUTO switch to OFF.
b.
Stop metering pump by turning MAN/OFF/AUTO switch on metering pump motor controller (Figure 9-6) to OFF.
NOTE
Chlorination unit continues to produce and store chlorine solution for later use. If
chlorination unit Is to be shut down completely, perform steps c and d.
c.
Close valves CU2, CU6, and CU10.
d.
Turn function switch on control cabinet (Figure 9-9) to OFF/RESET.
e.
After shutdown, perform following after operation checks:
(1)
Wipe components clean, especially flowmeters, indicators, control panels, and electrolytic cells.
(2)
Check for leaks, paying special attention to all joints, valves, fittings, and piping Report leaks to shift leader
so corrective action can be taken.
(3)
Check for damage, especially to pressure gauges, flowmeters, indicators, and control panels. Repair as
necessary.
(4)
Check for loose or missing securements and fasteners. Tighten or replace as necessary.
(5)
Check wiring for loose connections and frayed cables. Tighten or replace as necessary.
9-17 Emergency shutdown
9-17.1 General. The barge has two emergency shutdown modes (Chapter 3). One mode shuts down individual systems
such as the ventilation system or a diesel high pressure pump, and the other shuts down all barge operating systems.
Both modes are activated by pushing a red button protected by a metal guard. On individual system shutdowns,
either fuel or electrical power is shut off to that system only. On total shutdown, all fuel and electrical power is shut off to
all operating systems.
Seven red system shutdown buttons are located on the ROWPU space starboard bulkhead just aft of the personnel
door. These system shutdown buttons (Figure 3-16) control shore power, ventilation systems, ROWPU1 diesel HP pump,
ROWPU2 diesel HP pump, SAG, SSG2, and SSG1.
Six red total shutdown buttons are located as follows:
On ROWPU space starboard bulkhead aft of personnel door, above and forward of row of system shutdown
buttons.
Outside ROWPU space starboard door on weatherdeck.
Outside ROWPU space port door on weatherdeck
Inside ROWPU space port door to weatherdeck.
Outside dayroom door to weatherdeck.
Inside dayroom door to weatherdeck.
9-27