TM 55-1930-209-14&P-1
NOTE
Pressure set automatically fills reserve tank.
e.
Close power panel 1 circuit breaker 11P5 to provide power to pressure set motor controller.
f.
Position HAND/OFF/AUTO switch on pressure set controller to AUTO and pressure set automatically fills reserve
tank.
g.
When reserve tank is full, as shown on liquid level indicator, close DW16.
h.
When drinking water storage tanks are full, open drinking water valves DW11 and DW17. Pressure set supplies
onboard drinking water directly from storage tanks and bypasses pressure set reserve tank
14-11.6.2 Filling drinking water reserve tank from other vessel or shore supply
NOTE
If drinking water is not available from storage tanks, reserve tank can be filled from
other available drinking water supplies.
a.
Remove cap from water fill pipe located near port discharge valve DW15 on weatherdeck.
b.
Attach or insert hose from drinking water supply.
c.
Close valves DW13 and DW16.
NOTE
Use telephone headsets for communications between weatherdeck and void 3 port
d.
When reserve tank is full, as indicated by reserve tank liquid level indicator, stop filling tank.
e.
Reinstall cap on water fill pipe.
14-11.7 Supplying drinking water on barge from reserve tank
NOTE
Drinking water In reserve tank Is for use onboard barge when water is not available
from storage tank(s).
a.
Obtain sample of drinking water from reserve tank at sample valve. Check chlorine content according to
TM 5-6630-215-12. Add chlorine through chlorine fill on top of reserve tank if chlorine content is not between 2
and 5 ppm.
b.
Make sure filter cartridge is clean. Replace if necessary.
c.
Close valves DW11 and DW16.
d.
Open drinking water valves DW5, DW5A (on Barges 2 and 3 only), DW13, and DW17.
NOTE
Pressure set automatically supplies, on demand, drinking water to dayroom,
washdown stations, chlorination unit, and shower.
e.
Close power panel 1 circuit breaker 11P5 to provide power to pressure set motor controller.
14-25