TM 55-1930-209-14&P-11
Table C-1. Preventive Maintenance Checks and Services for Equipment Monitoring System (Continued)
B -
Before
D -
Daily
Q - Quarterly
D -
During
W -
Weekly
S - Semiannually
A -
After
M -
Monthly
A - Annually
INTERVAL
ITEM
PROCEDURES
EQUIPMENT
ITEM
TO BE
CHECK FOR AND HAVE
IS NOT READY/
NO.
INSPECTED
REPAIRED OR ADJUSTED
AVAILABLE IF
B D A D W M Q S A
AS NECESSARY
a. Check that batteries are secure and
Batteries and
that electrical cable fittings are tight.
cables are not
Use insulated tools to tighten as
secure and
necessary.
fittings not tight.
b. Check batteries for proper electrolyte
level. Add distilled water or clean tap
water to bring to proper level
c. Make sure battery charger select switch
is on FLOAT for normal charges and
voltmeter reads about 24V. The HIGH
switch setting is for rapid recharge
CAUTION
Do not allow battery charger to remain
on HIGH setting for more than 24
hours.
3
Keyboard Lamp
a. Perform keyboard lamp and alarm test
Keyboard lamp
and Alarm
as follows:
inoperable
1) Press EDIT key.
2) Press key 6 (KEYBOARD LAMP
TEST). All keyboard keys, except
ACK key, should light and alarm
should sound. Make sure all alarm
devices operate.
b. Using insulated tools, replace bad lamps Monitor does not
and fuses.
return to normal
operation
c. After completion of test, press EDIT key
to initiate normal monitoring.
NOTE
Keyboard lamp and alarm test may be
run
without
affecting
monitoring
anytime edit mode Is not in use.
C-4