TABLE 1
Capacity and Physical Data (Continued)
Direct Expansion Coil Data
Face Area, Sq. Ft. 5.47
Face Velocity, FPM
383
Fin Height, Inches
22 1/2
Fin Length, Inches
35
Number of Face Tubes
18
Total Number of Tubes
72
Number of Circuits
8
Tube O.D., Inches
1/2
Wall, Inches
.016
Fins per Inch
10
Compressor Data (Semi-Hermetic)
Cylinders
4
Motor Cooling Medium
Suction
Horsepower
5
R.L.A. @ 460 Volts
9.4
Bore, Inches
1.8125
Stroke, Inches
1.250
Displacement, CFM
13.1
Oil Recharge
5 pints
Refrigerant Pressure Protection
High Pressure Cut-In PSI
Manual Reset
Control Cut-Out PSI
295 + 5
Low Pressure Cut-In PSI
60 + 5
Control Cut-Out PSI
35 + 5
1.4.3
Table 2A defines the heat transfer data characteristics of the A.R.E. Model NAC-600 marine air
conditioner:
5