TM 55-1930-209-14&P-19
Table 17-4. Preventive Maintenance Checks and Services
for Workboat, Lifesaving, and Firefighting System (Continued)
B -
Before
D -
Daily
Q - Quarterly
D -
During
W -
Weekly
S - Semiannually
A -
After
M -
Monthly
A - Annually
INTERVAL
ITEM
PROCEDURES
EQUIPMENT
ITEM
TO BE
CHECK FOR AND HAVE
IS NOT READY/
NO.
INSPECTED
REPAIRED OR ADJUSTED
AVAILABLE IF
B D A D W M Q S A
AS NECESSARY
2
CO2 Hose
Reel Unit
WARNINGS
C02 (carbon dioxide) gas used as an extin-
guishing agent does not contain oxygen in
any form for supporting combustion or sus-
taining human life in breathing. Caution
must be used before entering any space
filled with C02 gas. Unless the space has
been thoroughly ventilated with fresh air, a
self- contained breathing apparatus must be
worn when entering enclosed areas where
C02 gas has been released.
When releasing C02, operators must stay
out of fumes and oxygen-starved area cre-
ated by the C02 gas.
Operators must hold release nozzle horn by
its handle or wear thick gloves to protect
hands from freezing to nozzle. C02 gas gen-
erates extreme cold which can cause per-
sonal injury.
The maximum safe storage temperature for
all C02 cylinders is 130 °F. To avoid acci-
dental release of C02 gas through activation
of the cylinder safety relief valve, ensure
that each cylinder is kept or stored in places
where the temperature will not reach critical
levels.
a. Visually check for damage to hoses and
Hoses or nozzles
other equipment and for obstructions to
obstructed or
discharge nozzles. Notify bargemaster or
damaged.
shift leader of damage or inoperability of
system.
CAUTION
C02 can cause corrosion of equipment.
Clean all materials with soapy water imme-
diately after use of this agent.
b. Clean hoses and other hardware with
soapy water.
17-22