TM 55-1930-209-14&P-3
Table B-1. Preventive Maintenance Checks and Services for ROWPU System (Continued)
B-Before
D-Daily
Q-Quarterly
D-During
W-Weekly
S-Semiannually
A-After
M-Monthly
A-Annually
ITEM
PROCEDURES
INTERVAL
TO BE
CHECK FOR AND HAVE
EQUIPMENT
ITEM
INSPECTED
REPAIRED OR ADJUSTED
IS NOT READY/
NO.
AS NECESSARY
AVAILABLE IF:
B D
A D W M Q
S
A
(e) Empty and clean glass collecting
bowl on bottom of engine
crankcase filter system as fol-
lows:
Pull down on metal tab of
cage surrounding bowl.
Unsnap wire cage on each
side of bottom of bowl.
Remove bowl and wipe with
clean cloth. Do not use abra-
sives.
Replace fuel filter in reverse
order.
8I
Pump V Belts
WARNING
To prevent electric shock, ensure battery
is disconnected before performing this
procedure.
NOTE
Refer to TM 55-1930-209-14&P-3-2, para.
6.2.10 for complete instructions and
illustrations on belt tensioning.
a. Check tension on pump V-belts. If they
appear to be slack, adjust tension.
1) Adjust HP pump V-belt as
follows:
Remove 32 mounting bolts and
lockwashers. Remove front V-belt
housing (two pieces).
Place a straight edge on V-belt in a
straight line with bearing bases.
Place tension meter pointer on the
line on the center of the front belt.
NOTE
Do not contact O-ring on tester stem.
B-30