TM 55-1930-209-14&P-8
Table 4-1. Fuel Oil System Troubleshooting (Continued)
Condition
Possible Cause
Suggested Action
4. Port and starboard
a. Monitoring system
a. Troubleshoot system as
tanks overflowed
malfunctioning
described in
TM 55-1930-209-14&P-11
b. Liquid level switch
b. Repair or
malfunctioning
replace switch
c. Fuel oil visual level
c. Unclog or repair
indicator clogged or
indicator
damaged
d. Tank filling operation not
d. Station crew-
being observed by crew-
member at tank
member
being filled
B. Transferring fuel oil from storage tanks to day tank (paragraph 3-3.2):
1. Fuel will not
a. Fuel oil transfer pump
a. Close circuit
transfer from port
circuit breaker 2P5
breakers
storage tank
power panel 1 open (OFF) or
P5 on switchboard open (OFF)
b. Pump not operating
b. Troubleshoot as
because:
follows:
(1) Motor controller off
(1) Start pump
(2) Fuse in motor
(2) Replace
controller blown
fuse
(3) Pump malfunctioning
(3) Troubleshoot
pump per
pages 5-8,
Appendix B
(4) Remote stop switch
(4) Repair or
malfunctioning
replace switch
(5) Liquid high level switch
(5) Repair or
malfunctioning
replace
high level
switch
c. Pump motor controller
c. Troubleshoot con-
malfunctioning (loose
troller as described
wiring, broken connectors,
in TM 55-1930-209-14&P-9
etc.)
d. FO valve(s) 8,10, 21 or 22
d. Open valve(s)
closed
e. Fuel filter clogged
e. Clean or change
filter
f. Fuel oil line or check
f. Isolate, clear
valve clogged or damaged
or repair clogged
line. Check valve
2. Fuel will not transfer
a. Fuel oil transfer pump cir-
a. Close circuit breaker
from starboard storage
cuit breaker 2P5 on
tank
power panel 1 open (OFF)
4-3