TM 55-2090-201-14&P
3-28.
SUPPLY PUMP ASSEMBLY, TYPE A AND B SEPARATORS.
This task covers:
a.
Test
b.
Removal
c.
Replacement
d.
Installation
INITIAL SETUP
Test Equipment
None
Tools
Tool Kit, General Mechanics
Material/Parts
Supply pump assembly
Sealing compound
Appendix C, Item No. 6
Equipment Condition
Personnel Required
1
LOCATION
ITEM
ACTION
R E M A R K S
Electrical shock or serious injury may result if
electric power to motor is not shut off prior to
performing maintenance on the supply pump assembly.
1.
a. Check flow rate indicator
for rate of flow.
Reading
on gauge should be between
2 and 5 gpm.
b. Check pressure gauges for
loss of pressure.
3-156