TM 10-4610-215-24
TM 08580A-24/2
c. Dissassembly. (Figure 3-12) (Refer to Schematic, Figure 1-12)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(13).
(8)
(9)
(10)
(11)
(12)
(13)
(14)
NOTE
The two motor starters described in this paragraph are similar,
except that the 1/3 hp model has only one overload relay;
however, disassembly procedures are identical.
Identify and tag all wires before disconnecting them for ease of
reassembly later.
Remove wires (1) from operating coil (2) and overload relay (3).
Remove wires (4) from overload relay (3) and contacts of stationary contact assembly (5).
If applicable, remove wires (6) from overload relays (7) and (8).
Remove two screws (9) from bus bar (10) and operating coil (2).
Remove bus bar (10) from operating coil (2).
Loosen captive screw (11) in base of operating coil (2).
Carefully remove operating coil (2) with movable contact support assembly (12) attached, from base
Slide movable contact support assembly (12) off of the operating coil (2).
Remove yoke (14) from operating coil (2).
Slide armature (15) out of slot in operating coil (2).
Remove two bolts (16) from stationary contact block assembly (5) and base (13).
Remove stationary contact block assembly (5) from base (13).
Remove movable contact (17) and spring (18) from movable contact support assembly (12).
Remove two screws (19) from overload relay mounting bracket (20) and base (13).
3-57