TM 10-4610-232-12
Table 2-13. Operator Preventive Maintenance Checks and Services (PMCS)
(Continued)
Item
No.
Interval
Item to
Check/Service
Procedure
Not Fully Mission Capable If:
82.
After
High Pressure
a. Inspect ratchets for binding.
Damage is observed.
Pump Tiedown
b. Spray ratchets with silicone spray.
Straps
83.
After
Air Compressor
Inspect for loose or missing mounting
Guard is loose or damaged.
Belt Guard
hardware.
84.
After
Air Compressor
Check oil level.
Oil level low.
Oil Level
85.
After
Air Blowdown
Check for air blowdown solenoid valve
Solenoid has oil leak.
Solenoid Valve
oil leakage.
86.
After
Media Filter
Check Media Filter level.
If measurement is less than 14 in.
or more than 18 in.
87.
After
Interior Electrical
Check for cuts, loose
Damage that would prevent
Cables.
connections/damaged connectors.
operation.
88.
After
Eyewash Station
If ROWPU has been in continuous
Solution is not replaced monthly
operation for a month, replace solution.
when in continuous operation.
89.
Weekly
Carbon
Check CO Monitor weekly for proper
Test unable to be performed.
Monoxide (CO)
calibration.
Monitor
90.
Weekly
Storage Boxes
Check for lose mounting hardware or
damage.
91.
Weekly
Hypochlorite
Clean and flush weekly.
Tank, Mixer, and
Tubing
92.
Weekly
Booster Pump
Inspect for loose mounting hardware
Cover
and damage to cover.
93.
Monthly
Chain Hoist
Spray with silicon spray.
94.
Monthly
High Pressure
Inspect for loose mounting hardware.
Guard is loose or damaged.
Pump Belt Guard
2-48.2 Change 12