TM 10-4610-232-12
4-13. RAW WATER PUMP POWER CABLE. This task covers:
a. Removal.
b. Repair.
c. Installation.
INITIAL SETUP.
Tools, see Appx B, Sec III. Ref Code (No.):
Tool Kit, General Mechanics (1)
Materials/Parts:
Rivets (TM 10-4610-232-24P)
Riveter, Hand (2)
Drill Motor and Bits (2)
Multimeter (2)
Equipment Condition:
ROWPU shutdown.
a. Refer to Figure 4-15 and disconnect cable by turning connector (1) 1/4 turn counterclockwise.
b. Install dust cap on ROWPU van connection.
a. Remove strap (2) from cable (3) by drilling out the rivet (4) and removing flat washer (5) and clamp (6).
b. Remove dust caps (7) by prying open S-hook (8).
Figure 4-15. Raw Water Pump Power Cable
4-95