TM 10-4610-232-12
1-11. EQUIPMENT DATA.
a.
Performance.
Brackish water (based upon TDS of 1000-15,000 at 77F (25C) water temperature:
Flow Rate ...........................................................................................................................................53 gpm (200 l/min)
Average Daily Production ...................................................................................................60,000 gallons (227,100 l)
Quality................................................................................................................................................20 to 200 ppm TDS
Fuel Consumption .........................................................................................................2.0 to 3.4 gph (7.5 to 12.9 l/hr)
Sea water (based upon TDS of 15,000-35,000 at 77°F (25°C) water temperature:
Flow Rate ....................................................................................................................................... 34 gpm (128.7 I/min)
Average Daily Production ...................................................................................................40,000 gallons (151,400 l)
Quality..............................................................................................................................................470 to 825 ppm TDS
Fuel Consumption ..........................................................................................................3 to 3.4 gph (11.4 to 12.9 l/hr)
Fresh water and NBC contaminated fresh water (based upon TDS of up to 1000 TDS at 77F (25°C) water temperature:
Flow Rate .............................................................................................................................................53 gpm (200 min)
Average Daily Production ...................................................................................................60,000 gallons (227,100 l)
Quality.................................................................................................................................................0.1 to 10 ppm TDS
Fuel Consumption .........................................................................................................2.0 to 3.4 gph (7.5 to 12.9 l/hr)
NOTE
When the temperature is lower than 75° F (24° C), the flow rate and daily production of
potable water may be less. This is due to viscosity effects.
b.
Operating Temperatures ........................................................................................................-25F to +110F (-32C to +43C)
c.
Storage Temperatures.
ROWPU less sensitive items ................................................................................................-28F to +145F (-33C to +63C)
Sensitive-items ...........................................................................................................................35F to +110F (+2C to +43C)
RO Elements
Polyelectrolyte
Sequestrant
Color Test Kit
Available Chlorine Color Comparator Test Kit
Turbidity Standards
NTP-A Cleaner
Membrane Cleaner Detergent
d.
Power Requirements ........................................................................................................................... 60 KW maximum demand
e.
Dimensions and Weight
(1)
ISO container fully packed...............................................................20 x 8 x 8 ft (6.1 x 2.4 x 2.4m), 15,100 lb (6849 kg)
.................................................................................................................................................................(MODEL WTA-060 ONLY)
.....................................................................................................................20 x 8 x 8 ft (6.1 x 2.4 x 2.4 m), 14,790 lb (6723 kg)
...............................................................................................................................................................(MODEL ROWPU-1 ONLY)
(2)
Mobility configured............................................................................................................. 8 x 13 x 30 ft (2.4 x 3.9 x 9.1 m)
(3)
ROWPU with generator mounted on trailer ready for transport and deployment.......................37,960 lb (17,215 kg)
.................................................................................................................................................................(MODEL WTA-060 ONLY)
..........................................................................................................................................................................37,650 lb (17,114 kg)
...............................................................................................................................................................(MODEL ROWPU-1 ONLY)
1-12 Change 12