TM 10-4610-239-10
TM 08580B-10/1
NOTE
MC Model 0996108001 top and second-from-bottom vessels have reverse flow direction. Open end of
brine seal should face chemical feed pump end of ROWPU.
(5)
Insert by hand the first R.O. element (2) into R.O. vessel (3) until brine seal (1) touches end of R.O.
vessel.
LEGEND:
1.
Brine Seal
2.
R.O. Element
3.
R.O. Vessel
NOTE
(MC) Direction of flow is indicated on the side of each element.
Figure 3-6. Element Replacement
(6)
Refer now to fig. 3-7. Place interconnector (1) on product water tube (2) of first R.O. element (3).
NOTE
Do not confuse interconnector with end connectors. End connectors have a lip on the outside.
3-21