TM 10-4610-239-24
TM 08580B-24/3
REMOVAL.
a. Loosen and remove two turnbuckles (1).
b. Remove six nuts (2) and six bolts (3) and three clamps (4) and three gaskets (5).
c.
Remove three connectors (6) from fittings (7).
d. Remove connector (8) from receptacle (9).
e. Remove 12 bolts (10), 12 lockwashers (11) and 12 flat washers (12). Discard lockwashers.
,
WARNING
Lack of attention or being in an improper position during lifting
operation can result in serious injury or death. Pay close
attention to movements of multimedia filter. Do not stand under
multimedia filter or in a position where you could be pinned
against another object. Watch your footing.
CAUTION
Uncontrolled sideways motion of multimedia filter during lifting
can cause damage to equipment. Two assistants are needed on
ROWPU to control motion of multimedia filter.
f.
Attach two crane hooks to two lifting eyes (13) and carefully lift multimedia filter (14) through opening in top
of ROWPU frame.
INSTALLATION.
WARNING
Lack of attention or being in an improper position during lifting
operation can result in serious injury or death. Pay close
attention to movements of multimedia filter. Do not stand under
multimedia filter or in a position where you could be pinned
against another object. Watch your footing.
CAUTION
Uncontrolled sideways motion of multimedia filter during lifting
can cause damage to equipment. Two people are needed on
ROWPU to control of multimedia filter.
a. Attach two crane hooks to two lifting eyes (13) and carefully lift multimedia filter (14) over opening in top of
ROWPU frame.
b. Slowly lower multimedia filter (14) while two assistants on ROWPU guide it into position.
c.
Install 12 flat washers (12), new lockwashers (11), and bolts (10).
d. Remove two crane hooks and install two turnbuckles (1).
e. Install connector (8) on receptacle (9).
3-117