TM 10-4610-240-24
TM 08580C-24/2
TO 40W4-13-22
2-64. CABLE ASSEMBLY W40 (GENERATOR) MAINTENANCE (MODELS WPES-1 AND WPES-3)
This task consists of:
a. Removal
b. Test
c. Installation
INITIAL SET-UP:
Tools Required
General Mechanics Tool Kit (Appendix B, Section III, Item 4)
Equipment condition
Reference
ROWPU shutdown (TM 10-4610-240-10).
Power shutdown (power source manual).
REMOVAL
WARNINGS
High voltage can cause burns and electrical shock. All electrical power must be
off before performing these procedures.
Lethal voltages are present at load connection board of the ROGEN during
operation. Do not attempt to connect or disconnect load leads while either
the ROGEN or the ROWPU are powered up or while the ROGEN is parallel to
another unit which is in operation.
a.
Open access cover (1) to access ROGEN terminal board (2).
b.
Loosen four terminal bolts (3), and disconnect four wires (4) from ROGEN terminal board (2).
c.
Loosen dust boot draw string (5), and pull power cable (6) through dust boot (7).
d.
At ROWPU junction box (8), loosen locking connector (9), and disconnect power cable (10) from ROWPU
junction box (8)
2-228